Why a Fire Sprinkler Pipe Froze in a Heated Stairwell — A Water Loss Investigation Case Study
On a January afternoon, a tenant in a seven-story mixed-use building called the property manager: water was pouring down an exit stairwell. A wet sprinkler pipe at the top of the stairwell had frozen and failed. When the sprinkler contractor opened the piping that day, they found it full of ice.
The puzzle was that the stairwell was heated. Two heat pumps served it, set at 70–72°F by a remote control kept in the management office so tenants could not change it. The property insurer retained CAE Forensic to determine why the pipe froze. CAE’s investigation traced the freeze to the stairwell’s ventilation, not to a heating failure or a defective part — and the findings supported the carrier’s pursuit of subrogation.

Summary of findings
- The leak came from a check valve and a sprinkler head on the wet sprinkler system at the top of the stairwell; the piping was full of ice
- The check valve’s inlet threads were damaged in the way expanding ice damages them — the valve body and sprinkler head had no defects
- A stair pressurization fan blew 4,000 cubic feet per minute (CFM) of unheated outdoor air into the stairwell about 2 feet above the sprinkler pipe
- Warming that air to the 40°F minimum required by NFPA 13 would take about 132,000 BTU/hr at the recorded low of 10°F — more than four times the 32,000 BTU/hr the stairwell heaters could supply
- The pipe froze because cold makeup air was blowing directly onto it; the makeup air fan should not have been configured this way
Background
The building was about five years old, with commercial tenants on the ground floor and apartments above. The basement, first, and second floors were protected by dry pipe sprinkler systems. Everything above, including the upper portion of the subject stairwell, was on a wet pipe system — pipes that stay full of water at all times.
Like most exit stairwells in multi-story buildings, this one had a stair pressurization fan on the roof. The fan pushes outdoor air into the stairwell so it stays at a higher pressure than the floors around it, which keeps smoke out of the stairs during a fire. This fan ran continuously and discharged into the stairwell at the ceiling of the 7th floor. Heat for the stairwell came from two ductless mini-split heat pumps — one on the 7th floor and one on the 1st.
The Investigation
There were three possible explanations: a defective component, a heating failure, or a condition built into the stairwell. CAE inspected the building, examined the removed parts, compared the installed equipment against the building’s mechanical drawings, and calculated the heat load the stairwell actually faced.
Ruling out a defective component
The building manager provided the check valve and sprinkler head the contractor had removed. Most of the water had come from the check valve, with a smaller leak at the sprinkler head. The check valve’s body showed no sign of failure, and the sprinkler head was intact. The damage was on the male threads of the valve’s threaded inlet connector.

Water expands about 9% when it freezes. In a closed, water-filled pipe, that expansion drives pressure high enough to force joints apart. The thread damage, the ice found in the piping, and the absence of any defect in the valve body or sprinkler head together established that the components failed because the water froze — not because a part was defective.
Where the cold air came from
At the top of the stairwell, the sprinkler piping ran near the ceiling, the 7th-floor mini-split was mounted on one wall, and the makeup air outlet sat at the ceiling — about 2 feet above the sprinkler pipe.

The stair pressurization fan on the roof was rated at 4,000 CFM. It drew outdoor air and delivered it into the stairwell without heating it, so the air entered at roughly the outdoor temperature. According to building management, the fan ran continuously.

Could the stairwell heaters keep up?
NFPA 13, the Standard for the Installation of Sprinkler Systems, requires spaces containing wet pipe sprinklers to be kept at or above 40°F. So the question became: how much heat does it take to warm 4,000 CFM of outdoor air to 40°F, and how much heat did the stairwell have?
CAE used the standard sensible heat equation from the ASHRAE Handbook — Fundamentals (Chapter 16, Ventilation and Infiltration). The calculation was run twice: once at the 10°F low recorded on the day of loss, and once at the 17°F winter design temperature published in the International Plumbing Code for the area — the temperature the building’s systems should have been designed to handle.
Shortfall: about 4× at the recorded low, about 3× at the design temperature
The result was not close. At the recorded low, warming the incoming air took more than four times the heat both mini-splits could produce. Even at the design temperature, it took about three times as much. That comparison assumes the best case — every BTU from both units, including the one six floors down, going into the makeup air.
Capacity was not the only problem. The makeup air outlet was closer to the sprinkler pipe than the 7th-floor heater was, so the coldest air reached the pipe before it could mix with heated air. Even a heater large enough on paper would have left the pipe at risk in freezing weather.
Was it an equipment substitution?
The mechanical drawings specified a fan and heat pumps from different manufacturers than the ones installed. CAE compared them. The installed fan had the same 4,000 CFM rating as the fan in the drawings, and the installed heat pumps had more heating capacity than specified (16,000 BTU/hr each, versus a maximum of 11,100 BTU/hr at 17°F in the drawings). The substitutions did not cause the freeze. The configuration itself — continuous, unheated outdoor air discharged next to wet sprinkler piping — could not keep the pipe above freezing.
Conclusions
CAE Forensic concluded to a reasonable degree of engineering certainty that:
- The sprinkler system leaked because the water in the piping froze
- The freeze was caused by low-temperature, unconditioned makeup air blowing into the stairwell close to the sprinkler piping
- The stairwell heating could not offset the cold air load, even in the best case
- The makeup air fan should not have been configured in this manner
The carrier pursued subrogation based on these findings.
Why this case matters for subrogation
- “Heated space” does not end the inquiry. Freeze losses are often closed as a heating or maintenance failure by the owner. Here, the heat was on and set at 70–72°F. The cause was air movement, which only an investigation of the building’s mechanical systems would reveal.
- Follow the air, not just the thermostat. Stair pressurization fans, outdoor air intakes, and exhaust openings can hold a pipe below freezing in a room that feels warm. Fire Engineering lists stair towers among the areas most prone to sprinkler freeze-ups.
- The removed parts proved the mechanism. Because the contractor kept the check valve and sprinkler head, CAE could confirm freezing and rule out a defective product. Had they been discarded, that question would have stayed open.
- Calculations turn an observation into a finding. Saying a fan blew cold air is an observation. Showing that the stairwell needed three to four times more heat than it had is a quantified, defensible conclusion.
- Drawings and submittals matter. Comparing the installed equipment against the design eliminated the equipment substitutions as the cause and kept the focus on the configuration.
For guidance on what to keep after a loss like this, see Evidence Preservation After a Mechanical Failure or Fire: A Guide for Adjusters and Attorneys.
For another water loss investigation involving hidden plumbing failures and duration of loss, see Two Leaks, Years of Damage: A Crawl Space Water Intrusion Investigation.
For how CAE tests competing explanations before reaching a conclusion, see The Scientific Method in Forensic Engineering: Why Rigorous Investigation Matters.
This case study is written for property and commercial insurance adjusters, subrogation professionals, property managers, and attorneys handling sprinkler freeze and water damage claims in multi-story buildings.
Questions adjusters and attorneys ask about frozen sprinkler pipe claims
Can a fire sprinkler pipe freeze inside a heated building?
Yes. A space can be heated and still have pipes that freeze if a stream of outdoor air is blowing across them. In this case a stair pressurization fan delivered 4,000 CFM of unheated outdoor air about two feet above a wet sprinkler pipe. On a 10°F day, warming that much air to 40°F takes about 132,000 BTU/hr, while the stairwell heaters supplied 32,000 BTU/hr combined. The pipe froze even though the stairwell heat was set at 70–72°F.
What temperature does NFPA 13 require for wet pipe sprinkler systems?
NFPA 13 requires the area around a wet pipe system to be maintained at or above 40°F (4°C). Where that cannot be done, the piping must be protected another way, such as a dry pipe or preaction system, a listed antifreeze system, or listed heat tracing.
What is a stairwell pressurization fan, and why can it freeze sprinkler pipes?
A stairwell pressurization fan, often called a makeup air fan, blows outdoor air into an exit stairwell to keep it at a higher pressure than the surrounding floors so smoke stays out during a fire. These systems are addressed in NFPA 92, Standard for Smoke Control Systems. Many run continuously and deliver outdoor air without heating it. If that air discharges near wet sprinkler piping, the pipe can be held below freezing even when the rest of the stairwell feels warm.
How does a forensic engineer prove a sprinkler leak was caused by freezing?
By combining independent lines of evidence: ice found in the pipe when it was opened, damage to the failed component that matches expansion from freezing rather than a manufacturing defect, weather records showing sub-freezing temperatures, and an engineering comparison of the space’s heat load against the heat available. In this case all four pointed the same way.
Is a frozen sprinkler pipe always the building owner’s responsibility?
No. Freeze losses are often treated as a maintenance or heating failure by the owner, but that is not always the cause. When the space was heated as intended and the freeze traces to how a system was designed or installed — such as an outdoor air outlet aimed at sprinkler piping — the loss may support subrogation against the parties responsible for that design or installation. The answer depends on the physical evidence and the engineering analysis.
What should an adjuster or property manager do after a sprinkler freeze leak?
Keep the failed components — ask the sprinkler contractor to save the removed valve, fittings, and sprinkler heads instead of discarding them. Photograph the leak location, nearby air outlets, heaters, and thermostat settings before anything is changed. Obtain the building’s mechanical and fire protection drawings and equipment submittals, and record weather data for the days before the loss. Contact a forensic engineer early, before repairs change the conditions. See CAE’s guide on evidence preservation after a mechanical failure.
