Bar chart comparing heat needed to warm stairwell makeup air to 40°F (132,000 BTU/hr at 10°F, 101,200 BTU/hr at 17°F) with 32,000 BTU/hr available from the stairwell heaters

Why a Fire Sprinkler Pipe Froze in a Heated Stairwell — A Water Loss Investigation Case Study

Case StudyWater DamageFire Sprinkler SystemsBy James Laird, PE, IAAI-CFI, CFEI, CVFI  ·  CAE Forensic Why a Fire Sprinkler Pipe Froze in a Heated Stairwell — A Water Loss Investigation Case Study On a January afternoon, a tenant in a seven-story mixed-use building called the property manager: water was pouring down an exit stairwell. A wet […]

Why a Fire Sprinkler Pipe Froze in a Heated Stairwell — A Water Loss Investigation Case Study Read More »

2019 Honda CR-V front-end and passenger-side collision damage — CAE Forensic automotive brake inspection investigation

Brake Failure Claim or Driver Inattention? How EDR Data and Physical Inspection Tell the Complete Story

Case Study Automotive EDR / Crash Data Insurance Defense By James Laird, PE, IAAI-CFI, CFEI, CVFI  ·  CAE Forensic Brake Failure Claim or Driver Inattention? How EDR Data and Physical Inspection Tell the Complete Story A driver rear-ended a vehicle on the interstate at highway speed and claimed the brakes had failed. The insurance carrier

Brake Failure Claim or Driver Inattention? How EDR Data and Physical Inspection Tell the Complete Story Read More »

Severely deteriorated crawl space framing lumber with organic growth from long-term water damage — duration of loss investigation CAE Forensic Washington

Two Leaks, Years of Damage — A Crawl Space Water Intrusion Investigation

Case Study Water Damage Plumbing Failure Duration of Loss By James Laird, PE, IAAI-CFI, CFEI, CVFI  ·  CAE Forensic Two Leaks, Years of Damage — A Crawl Space Water Intrusion Investigation When a tenant noticed a soft spot in the master bathroom floor, a plumber found two active water leaks in the crawl space below.

Two Leaks, Years of Damage — A Crawl Space Water Intrusion Investigation Read More »

Subject gas range removed from home after broiler explosion — forensic mechanical engineering inspection

A New Stove, A First Use, An Explosion: How a Professional Installation Left a Propane Bomb Inside a Brand-New Gas Range

The homeowner had done everything right. He bought a brand-new gas range from a national appliance retailer, paid for professional installation, and had it converted from natural gas to propane on the same day it was delivered. For months, everything worked perfectly. The stovetop burners lit without issue. Dinner was made. The kitchen was fine.

A New Stove, A First Use, An Explosion: How a Professional Installation Left a Propane Bomb Inside a Brand-New Gas Range Read More »

compact tracked loader destroyed by fire — CAE Forensic heavy equipment fire investigation

What Caused a Tracked Loader Fire After a Service Visit — A Fire Investigation Case Study

Case Study Fire Investigation Heavy Equipment By James Laird, PE, IAAI-CFI, CFEI, CVFI  ·  CAE Forensic What Caused a Tracked Loader Fire After a Service Visit — A Fire Investigation Case Study A compact tracked loader caught fire on the first day of operation after returning from a service shop. The operator had been using

What Caused a Tracked Loader Fire After a Service Visit — A Fire Investigation Case Study Read More »